Air circuit breaker DMX³ 6300 lcu 100 kA - fixed version and electronic protection unit - 4 poles - 6300A

DMX³ 6300 LEGRAND

Air circuit breaker DMX³ 6300 lcu 100 kA - fixed version and electronic protection unit - 4 poles - 6300A

REF. 028961 EAN. 3245060289614
DMX³ air circuit breakers offer optimal solutions to answer to protection requirements on the origin of the low voltage electrical installation (IEC/EN 60364-1) up to 6300A.
You can only compare 4 products, you must remove 1 to add this one

Technical characteristics

Rated permanent current Iu 6300 A
Rated voltage (Min-Max) 230-690 V
Rated short-circuit breaking capacity Icu at 400 V, 50 Hz 100 kA
Overload release current setting (Min-Max) 2520-6300 A
Adjustment range short-term delayed short-circuit release (Min-Max) 3780-63000 A
Adjustment range undelayed short-circuit release (Min-Max) 12600-100000 A
Device construction Built-in device fixed built-in technique
Integrated earth fault protection Yes
Suitable for DIN rail (top hat rail) mounting No
DIN rail (top hat rail) mounting optional No
Number of auxiliary contacts as normally closed contact 4
Number of auxiliary contacts as change-over contact 4
With switched-off indicator Yes
With integrated under voltage release No
Number of poles 4
Position of connection for main current circuit Back side
Type of control element Push button
Complete device with protection unit Yes
Motor drive integrated Yes
Motor drive optional Yes
Degree of protection (IP) IP30

Product environmental data

Product carbon footprint
Estimation of the Global Warming Potential (kgCO₂eq) emitted during the Manufacturing phase of the product life cycle according to sector methodology
725.376
Carbon footprint Manufacturing phase (A1-A3) (kg CO2 eq.)

Documentation

11 documents
Technical Guide
Y2958H.pdf pdf (88.32 Mo)
Technical Sheet
Technical Sheet
Y2687H.pdf pdf (11.91 Mo)
Technical Guide
Technical Guide
Technical Guide
Technical Guide
LE08866AE.pdf pdf (9.08 Mo)
Technical Sheet
2 documents
RoHS DIRECTIVE
REACH DECLARATION
1 document
3D Autocad
028961.dwg dwg (0.19 Mo)
1 document
Catalogue Commercial Page
ex223001_0224.pdf pdf (0.04 Mo)
1 document
Agreement
OC / CB-67052 (0.6 Mo)
1 document
Software
SELECT AN ACTION